  1. A Primer On The Elements Of Fire Protection Water Supplies

    Leave a Comment

    Get primed!

    Fire protection water supplies can be made up of one or more common elements, including tanks, pumps, water sources and water systems. Sometimes elements are used together to develop an adequate supply for fire protection.

    An adequate water supply for a fire protection system will meet the needs of the fire protection system (plus safety factor) in three terms: (more…)

  2. Know a Fire Sprinkler, Like a Boss – Part 2

    Leave a Comment

    In Part 1, we looked at the basic parts of a fire sprinkler and took a closer look at other parts including heat responsive elements, wrench bosses, and kick springs. In this part, we’ll look at k-factors and deflectors.

    K-Factor and Orifice Size

    K-factor is a characteristic that relates water pressure to flow rate from the sprinkler, represented as k in the equation Q = k√P, where Q is flow (gpm) and P is pressure (psi).

    If we supply water at 50 psi to a k-factor 5.6 sprinkler, the flow rate is 40 gpm. If we supply 50 psi water to a K25 sprinkler, the flow rate is 177 gpm. There are now sprinklers as large as K33.6, which would flow 238 gpm given 50 psi – big difference from the K5.6!

    The most common k-factors are 5.6, 8.0, 11.2, 14, 16.8, 22.4 and 25.  There are smaller and larger k-factors than these.  For reference, K5.6 and possibly K8.0 are most often found in (more…)