  1. In Cahoots – Interconnections of Fire Protection Systems with Ancillary Equipment

    Leave a Comment

    Fire protection is an expanse that I am both fascinated by and passionate about. To prove it, I could show you my sprinkler collection… the old ones, the new ones, the sizes, the features!  But instead, I will share some information to show you the relationship between fire protection systems and other systems that you may have never thought about!

    Fire protection, suppression, and alarm systems often do not act alone. They can be in cahoots with life safety systems or other equipment or building systems to mitigate fires and help firefighters. Many, but not all, of these functions are associated with fire alarm systems. Many, but not all, of these functions are customary and expected. Some of these functions will automatically reset when the alarm or system is reset, but not all! (more…)

  2. Dig into Underground Fire Water Piping and Appurtenances

    Leave a Comment

    Many sites that are protected by fire sprinklers will have at least some amount of private underground fire water piping. Its purpose is to make water available for fire protection or suppression at a needed flow and pressure. Its presence is usually quietly evidenced by the connected objects that occasionally surface along its course, like valves, fire department connections and private hydrants, termed appurtenances. Underground water piping commands attention, though, when (more…)

  3. A Primer On The Elements Of Fire Protection Water Supplies

    Leave a Comment

    Get primed!

    Fire protection water supplies can be made up of one or more common elements, including tanks, pumps, water sources and water systems. Sometimes elements are used together to develop an adequate supply for fire protection.

    An adequate water supply for a fire protection system will meet the needs of the fire protection system (plus safety factor) in three terms: (more…)

  4. Know a Fire Sprinkler, Like a Boss – Part 2

    Leave a Comment

    In Part 1, we looked at the basic parts of a fire sprinkler and took a closer look at other parts including heat responsive elements, wrench bosses, and kick springs. In this part, we’ll look at k-factors and deflectors.

    K-Factor and Orifice Size

    K-factor is a characteristic that relates water pressure to flow rate from the sprinkler, represented as k in the equation Q = k√P, where Q is flow (gpm) and P is pressure (psi).

    If we supply water at 50 psi to a k-factor 5.6 sprinkler, the flow rate is 40 gpm. If we supply 50 psi water to a K25 sprinkler, the flow rate is 177 gpm. There are now sprinklers as large as K33.6, which would flow 238 gpm given 50 psi – big difference from the K5.6!

    The most common k-factors are 5.6, 8.0, 11.2, 14, 16.8, 22.4 and 25.  There are smaller and larger k-factors than these.  For reference, K5.6 and possibly K8.0 are most often found in (more…)