  1. Know a Fire Sprinkler, Like a Boss – Part 2

    Leave a Comment

    In Part 1, we looked at the basic parts of a fire sprinkler and took a closer look at other parts including heat responsive elements, wrench bosses, and kick springs. In this part, we’ll look at k-factors and deflectors.

    K-Factor and Orifice Size

    K-factor is a characteristic that relates water pressure to flow rate from the sprinkler, represented as k in the equation Q = k√P, where Q is flow (gpm) and P is pressure (psi).

    If we supply water at 50 psi to a k-factor 5.6 sprinkler, the flow rate is 40 gpm. If we supply 50 psi water to a K25 sprinkler, the flow rate is 177 gpm. There are now sprinklers as large as K33.6, which would flow 238 gpm given 50 psi – big difference from the K5.6!

    The most common k-factors are 5.6, 8.0, 11.2, 14, 16.8, 22.4 and 25.  There are smaller and larger k-factors than these.  For reference, K5.6 and possibly K8.0 are most often found in (more…)

  2. Know a Fire Sprinkler, Like a Boss – Part 1

    Leave a Comment

    In this blog we’ll take a look at the basic and some of the less-known parts of fire sprinklers, with more to come in a later post.

    Here are the basic parts of the fire sprinkler, shown on a pendent glass bulb sprinkler and an upright solder element (“fusible link”) sprinkler:

     

    Let’s take a closer look to learn about some of the less known parts, and also look at two types of sprinklers disassembled. Included in parentheses are some of the different names for some of these parts. (more…)

  3. GREASE Is The Word…Ensuring Proper Functioning of Wet Chemical Fire Protection Systems in Commercial Cooking Operations

    Leave a Comment

    Cooking equipment is the leading cause and is responsible for over half of fires in eating and drinking establishments (see Warren expert Chad Jones’ 2020 blog, Structure Fires in Eating and Drinking Establishments, for further reading on fire causes and NFPA 96 on duct inspection and cleaning). Fire extinguishing systems are also routinely provided over GREASE-producing cooking appliances. So why are some of these fires still so bad? GREASE is the word. (more…)

  4. Warren Forensics Celebrates 20 Year Anniversary

    Leave a Comment

    It makes me proud as the founder of Warren Forensics to announce that we have crossed another milestone in the history of our company. On February 1, 2017, we will have been in business for twenty years. I am particularly proud of our team of professional engineers and consultants who have worked on your forensic engineering cases and communicated, with authority, fact-based opinions you could trust. (more…)

  5. Injury on Power Buggy

    Leave a Comment

    When an operator is thrown from a ride-on vehicle when it tips over, such as a mud buggy, serious injury or death can result. In one such case we investigated, the issue centered on the maintenance of the vehicle, specifically whether a maladjusted hydrostatic drive caused the braking mechanism to malfunction. (more…)